ForewordThis service manual is the result of thededication of The Dometic Corporation andits engineers in giving service people thenecessary instructi
7.3 THERMOSTATOn the LP gas mode, full line pressure is directedthrough the thermostat to the burner until the thermostatsenses that the refrigerator
7.8 CROSSOVER TUBEThe crossover tube is located at the top of the flue tubeand is attached with a screw. It must be properlyattached or flame outage c
SECTION 9OTHER9.1 LEVELINGLeveling is one of the requirements for proper operationwith absorption refrigerators. The absorption designutilizes no mech
9.3 AIR LEAKSCheck the gasket on the doors to be sure of a positiveair seal. A simple method to check gaskets is to closethe door on a dollar bill, th
CONTENTSPAGE NO.RM2150,2190,2201 SERIES DIAGNOSTIC FLOW CHART. . . . . . . . . . . . . . . . . . . . . . . . . . . . .1SECTION 1OPERATION1 .1 RM2150
This program will address the most common system problems associated with the RM2150/2190/2201 ManualRefrigerators supplied by The Dometic Corporation
REFERSYMPTOMCAUSESECTION STEP8. Insufficient cooling on AC - coolsAC Volts 2properly on other mode(s). (RM2201) Heating Element3Thermostat 5.59. Insuf
SECTION 11 .1 RM2150 OPERATIONA.1)2)3)4)5)6)GAS OPERATIONSet 12 volt switch to “OFF”.Turn gas handle to left (so that handle is inline with gas valve
1.2 RM2190 OPERATIONGasInletConn1)2)3)NOTE: The gas and electric controls are located at therear of the refrigerator and are accessible through thelow
1.3 RM2201 OPERATION115 VoltSUPPLYThermostat\3A.1)2)3)4)5)6)GAS OPERATIONRotate selector to “OFF” position.Turn gas handle to the left.Turn gas thermo
SECTION 2AC VOLTAGE REQUIREMENTSThe refrigerator is a 120 volt AC, 60 Hz appliance. Theproper operating range is 100 to 132 volts. Check theAC volts a
NOTE: It will take a veryprecise ohm meter to accu-rately read this measure-ment. If a precise ohmmeter is not available, acontinuity reading willindi